The EnviroAlert ® EA-400 critical-environment monitoring device provides visibility of up to 4 environmental factors including temperature, humidity and water detection. When a condition deviates from the predetermined threshold both visual and audible notifications occur. When integrated into a security panel, the system allows for the real-time notification of an incident and immediate corrective action.
Features
- Simultaneous monitoring of 4 sensors
- Easy to read LCD display
- 8 event alarm memory, including time and date
- Auxiliary output relay for local audible alarm
- Auxiliary alarm silence feature with 10 minute timer
- Offset sensor calibration adjustment
- Tamper proof lock setting
- Alarm notification via dry contact relay to any alarm panel
Product Specifications
Power Requirements | 11 to 14 VDC @ 200mA (EA400-12) 23 to 26 VDC @ 200mA (EA400-24) |
Unit Operating Temperature | 32° to 122°F (0° to 50°C) |
Low/High Limit Adjust Range | -58° to 299°F (-50° to 150°C) |
Alarm Outputs | 4 Form C Relays (N.O./N.C.) 1A @ 30 VDC (Configurable) |
Auxiliary Alarm Output | 1 Form C Relay (N.O./N.C.) (Non-Configurable) |
Alarm Time Delay | 0 to 120 minutes (program independently for each zone) |
Console Dimensions | 6 x 4.75 x 1.25″ (15.24 x 12.07 x 3.18 cm) |
EA-400 Quick Start Guide EA-400 Spec Sheet
English Manual
French Manual
German Manual
Italian Manual
Spanish Manual
White Papers
EnviroAlert Limit and Hysteresis Settings
Temperature System Validation
Prop 65 Notice for Californians
Product Certifications
- RoHS WEEE
- TUV
- FCC
- CE