Digital TempAlert 4-zone (DTA-4)
[PN# **DISCONTINUED**]
Part #1105. Four zone temperature monitoring - Microprocessor controlled.
The model DTA-4 offers precise temperature monitoring of four channels (zones) through microprocessor-controlled console. It scans and updates each zone 15 times per minute to monitor for potentially damaging temperature changes.
The DTA-4 is capable of measuring any temperature from -67 to +300 F (-55 to +150 C) based on your choice of remote sensor probe (see accessory options). If temperature in any of the monitored areas rise or fall below your preset limits, the unit will provide a relay contact change which can activate any type of alarm panel, telephone dialer, wireless alarm system, etc.
This model has been discontinued. Please use the EnviroAlert EA400 as a replacement.
|
|
Typical Applications:
- Residential or Vacation Homes
- Commercial Buildings
- Office and Computer Areas
- Unattended Buildings
- Greenhouses & Animal Buildings
- Freezers and Refrigerated Rooms
- Buildings with Controlled Climates
|
Features:
- Microprocessor-controlled design
- 12 to 14 VDC powered
- (4) Independently adjustable high and low set points
- Large LCD display read in F or C
- Provides (4) SPDT output - one for each zone
- Supervise remote sensor probes up to 500 ft
- Easy surface mount installation
- One year parts and labor; subject to conditions of limited warranty.
|
Accessory Options:
- Standard Temp. probe (no cable. Not for freezers or coolers) P/N 1106
Temp Range: +32 to +220 deg F (0 to +105 deg C).
- Low Temp. Sensor probe for coolers, etc. (15 ft. cable) P/N 1107
Temp Range: -67 to +220 deg F (-55 to +105 deg C).
- High Temp. Sensor probe for hot & dry areas. (6 ft. cable) P/N 1108
Temp Range: -67 to +300 deg F (-55 to +149 deg C).
- High/Low Liquid Temp. Sensor probe. (3 ft. cable) P/N 1109
Temp Range: -67 to +300 deg F (-55 to +149 deg C).
- 1/2" NTP Thread Temp. probe. (3 ft. cable) P/N 1109A
Temp Range: -67 to +300 deg F (-55 to +149 deg C).
- Audible Alarm Module (Model BZ-5) P/N 1183
Voltage: 5VDC @ 3mA.
- Accessory Time Delay Module (Model TDL-120). P/N 1193
Adjustable Delay Range: 1 to 120 minute.
- 3 Gang Surface Mounting Box P/N 1110
- Wall Transformer P/N 1111
Voltage: 110 VAC - 12VDC regulated, 300mA.
|
Specifications:
- Control Unit Display Range (Maximum): +32 to +130 F (0 to +54 C)
- Low or High Limit Adjust Range *: Sensor Dependent
- Recommended Sensor Cable: 18 - 24 AWG twisted Pair (shielded or unshielded)
- Minimum Span (Rec. dist. between high & low set points.): 4 F (2.2 C)
- Temp/RH Accuracy of Probes: +/-3 F (+/-1.7 C) For Probes #1106, 1107, M-001-0014
+/-0.5 F (+/-0.28 C) For Probes #1109, 1109A
+/-5 % for Probe 1128
- Temp/RH Accuracy of Control Unit: £ 2%
- Inputs & Scan Rate: 4 inputs (zones) ‚ Each zone is sampled 15 times per minute
- Temp/RH Sensing Element & Response Time: Linear Transducer - Sensor Dependent response time
- Outputs (not for high voltage use): 4 SPDT relays ‚ 1 Amp @ 30 VDC (not for direct high voltage switching)
- Input Voltage Requirements: 12 to 14 VDC @ 200mA
- Transistor Output Rating: 100 mA @ 12 VDC
- Control Box Material: ABS
- Dimensions & Weight: 6.55" x 4.70" x 1" (16.6 cm x 11.9 cm x 2.5 cm) ‚ 1 Pound (0.45 kg)
- Mounting: Surface Mount or 3-gang box (1110) 3 gang surface mount box
|
* NOTE: For assistance in ordering our products, please contact our customer service staff by phone, fax or email.
|